Pressure Sensing Switch; Type Adjustable, Differential; Operating Pressure Rating 0.5 PSIG; Differential Pressure Rating 0.02 Inch WC; Pressure Media Air; Contact Configuration SPDT 2-Circuit; Contact Rating 277 Volt AC 15 Amp, 115/277 Volt AC 300 Volt Amp (Pilot Duty); Connection Type 1/4 Inch Outer Diameter Rigid or Semi Rigid Tubing, Screw Terminal; Application Sensing Static Pressure Drop Across Filter; Temperature Rating -40 to 180 Deg F; Set Point Pressure Rating 0.05 to 12 Inch WC; Conduit Opening Size 7/8 Inch Diameter; Includes Electronic Air Cleaner, Remote Status Indicators, Alarm and Control Circuit
Temperature Rating -40 to 180 Deg F; Set Point Pressure Rating 0.05 to 12 Inch WC; Conduit Opening Size 7/8 Inch Diameter; Includes Electronic Air Cleaner, Remote Status Indicators, Alarm and Control Circuit
Features/Benefits
The 2374 series differential pressure switches are sensitive and reliable devices for remotely sensing the operation of fans and blowers associated with ducted ventilation system