Aquastat Controller; Type 3/8 Inch Diameter x 2-7/8 Inch Length Copper Bulb, 1-1/2 Inch Length Capillary, Direct Horizontal/Vertical Well Immersion, High/Low Limit; Temperature Range 100 to 240 Deg F; Maximum Temperature Rating 150 Deg F; Contact Rating 8 Amp at 120 Volt AC/5.1 Amp at 240 Volt AC (Full Load), 48 Amp at 120 Volt AC/30.6 Amp at 240 Volt AC (Locked Rotor), 0.25 Amp at 0.25 to 12 Volt DC (Millivolt); Contact Configuration SPST, Contact Break on Temperature Rise; Connection Type 3/4 Inch Conduit, Screw Terminal; Application Boiler, Storage Tank; Approval UL, CSA; Overall Dimension 2 Inch Width x 2-1/8 Inch Depth x 5-5/8 Inch Height; Differential Temperature Rating 5 to 30 Deg F (Adjustable); Pressure Rating 200 PSI (Capillary Bulb), 255 PSI (Immersion Well); Sensing Bulb Fill Liquid? Toluene or Silicone Oil; Includes Stop Factory Set at 240 Deg F, 123869A 1/2 Inch Well
Overall Dimension 2 Inch Width x 2-1/8 Inch Depth x 5-5/8 Inch Height; Differential Temperature Rating 5 to 30 Deg F (Adjustable); Pressure Rating 200 PSI (Capillary Bulb), 255 PSI (Immersion Well); Sensing Bulb Fill Liquid? Toluene or Silicone Oil; Includes Stop Factory Set at 240 Deg F, 123869A 1/2 Inch Well
Features/Benefits
Totally enclosed micro switch snap acting switches operate on temperature rise to set point Visible control point scale and external adjustment screw permit easy setting Direct or well immersion of the sensing element Horizontal or vertical insertion of the sensing element Remote bulb model may be used to sense air temperature in ducts and in outside air sensing application